Transducers |

Technical Detail:
- Model : SC 4W
- Type : 4 - wire
- Input : AC Amp from CT
- Input ranges : 0- 1 Amp / 0-5 Amp from CT
- Output : 4-20 mA, 0-20 mA, 0-5 V,0-10 V,
- Output ripple : Less than ± 0.25% of span (i.e. 0.05 mA) R.M.S
- Load on Output : 0 -700Ù (for mA O/p),> 100 K Ù (for Volt O/p)
- Isolation : Galvanic isolation
- Linearity : Within ±0.25% of Span
- Accuracy : Better than ±0.25% of F.S.
- Power fuse : 0.25 Amp
- Line voltage : 0.1% (within ±10%
- Response : Less than 1 sec.
- Anti-Humidity : Acryform conformal coating Treatment On PCB.
- Insulation Strength : Tested at 2.0 KV for all possible combination for one
- minute & at 500 VAC between electronics & earth.
- Drift : Within ±0.5% for 3 months
- Temp. Drift : ± 0.05% of Span per °C
- Power Supply : 110 / 230 VAC ±10%, 50 Hz
- Operating ambient Temperature& Humidity : 0 to 55° C & 5 to 95% Rh
- Mounting : Din rail / Field (Imported ABS plastic)
- Terminal : Suitable for upto 2.5 sq. mm Cable
- Adjustment : Zero & span are adjustable by two individual trim pots.